GAMMA RADIATION RANGE:
0.01 mR/hr to 1000 R/hr (0.1 μSv/hr to 10 Sv/hr)
RADIATION DETECTOR:
energy compensated G-M
HIGH ALARM THRESHOLD:
adjustable throughout entire detection range, meeting or exceeding
threshold triggers relays and ethernet warnings
LOW ALARM THRESHOLD:
adjustable throughout entire detection range, radiation levels below
threshold triggers relays and ethernet warnings
ETHERNET:
RJ-45 connector for 10/100 Base T Ethernet network
EXTERNAL SENSOR:
for external intrusion detection, triggers relays and ethernet warning
RELAYS:
fail-safe activated form C (common normally open, and normally
closed) relays for radiation alarm and tamper conditions, internal
tamper microswitch activates relays and ethernet warning whenever
the enclosure is opened
LED INDICATORS:
Green = OK
Red = indicates either radiation or
tamper/intrusion alarm
CONSTRUCTION:
ABS plastic, flammability rated UL94V-0
MOUNTING:
wall-mounted using four each #8 screws, not supplied; tamper-proof
screws recommended
POWER INPUT:
12 Vdc input (universal wall adapter supplied), 1.0 amp, 12 W
maximum
SIZE:
5.3 x 5.7 x 3.8 in (3.5 x 14.5 x 9.7 cm) (H x W x L)
Webpage and Service Software
COMMUNICATION:
Uses TCP/IP for basic communication across an Ethernet (LAN) Local Area
Network.
SERVICE:
Program runs in the background any time the computer is turned on.
Allows more complete 24/7 datalogging and webpage access.
WEBPAGE:
accessible by any network user with proper permissions using a standard
web browser like Internet Explorer or Mozilla Firefox
WEBPAGE WINDOWS:
Current Status - current status and reading of all
or selected area monitors
Incident Summary - list of alarms or failure
messages of all or selected instruments over a specified time/date range
Timeline Data - graph of a particular instrument’s
radiation readings over a specified time/date range
E-MAIL SUPPORT:
Alarms can immediately notify responsible personnel. Three sets of 10
e-mail addresses are available separated by shift number and by alarm
category.
CAMERA SUPPORT:
Optional Ethernet cameras can capture a picture of what triggers the
alarm.